Introduction
To
prevent the possibility of fire or explosion inside the enclosure
of energized electrical equipment, a protective gas supply is used
to dilute potentially flammable materials to an acceptable level,
creating a safe area for the electrical equipment within the enclosure.
Positive pressure prevents the ingress of flammable materials in
the surrounding atmosphere from entering into the enclosure, as
long as positive pressure is maintained. This technique of preventing
and protecting electrical equipment from possible fire and explosions
is commonly known as purging. Purge Solutions offers a type Y&Z -
Purge Indicator for monitoring electrical equipment in Division
2 and / or Zone 2 hazardous areas and three (3) different type X -
Purge Controllers for monitoring and controlling power to electrical
equipment in Division 1 and / or Zone 1 hazardous areas.
For Division
2 and / or Zone 2 hazardous areas Purge Solutions offers the CYCLOPS
Y&Z - Purge Indicator, which monitors purge pressure in one
(1) pressurized enclosure. The CYCLOPS
Y&Z - Purge Indicator comes standard with a green LED visual
indicator for local evidence of enclosure purge pressure, a dry-contact
output for remote monitoring of enclosure pressure, and the enclosure
exhaust vent, which is an integrated part of the CYCLOPS's casing.
The CYCLOPS Y&Z - Purge
Indicator mounts directly to the enclosure being purged.
This means no additional holes, sheet metal, or plumbing is required
for installation of the CYCLOPS
Y&Z - Purge Indicator. If all equipment in the protected enclosure is approved for
Division 2 and / or Zone 2 locations, the Cyclops Y&Z - Purge Indicator can be used for
type "Y" purging.
The first type
X - Purge Controller offered by Purge Solutions is the CYCLOPS
X - Purge Controller for use in Division 1 and / or Zone
1 hazardous areas, which monitors purge pressure, exhaust vent flow,
and controls electrical power and pre dilution purge time of one
(1) pressurized enclosure. The CYCLOPS
X - Purge Controller comes standard with a green and red
LED visual indication for local evidence of enclosure purge pressure,
dry-contact outputs for remote monitoring of enclosure pressure,
and the enclosure exhaust vent, which is an integrated part of the
CYCLOPS's casing. Also standard are a maintenance switch, which allows power to be
available to the electronics located in the monitored enclosure for maintenance
or service and a power disconnect switch for applications where disconnecting power to the electronics
located in the monitored enclosure would make for a more hazardous condition. The CYCLOPS
X - Purge Controller mounts directly to the enclosure being
purged. This means no additional holes, sheet metal, or plumbing
is required for installation of the CYCLOPS
X - Purge Controller.
The second type
X - Purge Controller offered by Purge Solutions is the TRYCLOPS
X - Purge Controller also for use in Division 1 and / or
Zone 1 hazardous areas, which monitors purge pressure, exhaust vent
flow, and controls electrical power and pre dilution purge time
for one (1), two (2) or three (3) pressurized enclosures. The TRYCLOPS
X - Purge Controller (XP Version) comes standard with a green and red LED visual
indication for local evidence of enclosure purge pressure and dry-contact outputs for remote monitoring of enclosure pressure.
Also standard are a maintenance switch, which allows power to be available to the electronics located in the monitored enclosure
for maintenance or service and a power disconnect switch for applications where disconnecting power to the electronics located in the
monitored enclosure would make for a more hazardous condition.
The TRYCLOPS
X - Purge Controller was specifically designed for use with multiple enclosure systems
such as analyzers. Both mount in the general area of the enclosure(s) they will be monitoring and come standard with a purge
exhaust vent for each enclosure the TRYCLOPS
X - Purge Controller will be monitoring.
|